Hp Insight Management for Tivoli Bedienungsanleitung Seite 67

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 270
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 66
Appendix B: HP SNMP events 67
Trap types Rules file Description
Netcool
severity
CpqCmcStatusHumidity:normal
CpqCmcStatusHumidi
ty.2
Clear (0)
CpqCmcStatusHumidity:overMax
CpqCmcStatusHumidi
ty.3
Major (4)
CpqCmcStatusHumidity:underMin
CpqCmcStatusHumidi
ty.4
Major (4)
CpqCmcStatusHumidity:noSensor
CpqCmcStatusHumidi
ty.5
Minor (3)
CpqCmcStatusHumidity:error
CpqCmcStatusHumidi
ty.6
Critical (5)
cpqCmcalarmInput1 (153007)
This event occurs when the door
or side panel of the rack is
opened (access point #1).
——
cpqCmcStatusInput1:closed
cpqCmcStatusInput1.
2
Clear (0)
cpqCmcStatusInput1:open
cpqCmcStatusInput1.
3
Minor (3)
cpqCmcStatusInput1:noSensor
cpqCmcStatusInput1.
4
Minor (3)
cpqCmcalarmInput2 (153008)
This event occurs when the door
or side panel of the rack is
opened (access point #2).
cpqCmcStatusInput2:closed
cpqCmcStatusInput2.
2
Clear (0)
cpqCmcStatusInput2:open
cpqCmcStatusInput2.
3
Minor (3)
cpqCmcStatusInput2:noSensor
cpqCmcStatusInput2.
4
Minor (3)
cpqCmcalarmInput3 (153009)
This event occurs when the door
or side panel of the rack is
opened (access point #3).
cpqCmcStatusInput3:closed
cpqCmcStatusInput3.
2
Clear (0)
cpqCmcStatusInput3:open
cpqCmcStatusInput3.
3
Minor (3)
cpqCmcStatusInput3:noSensor
cpqCmcStatusInput3.
4
Minor (3)
cpqCmcalarmInput4 (153010)
This event occurs when the door
or side panel of the rack is
opened (access point #4).
cpqCmcStatusInput4:closed
cpqCmcStatusInput4.
2
Clear (0)
cpqCmcStatusInput4:open
cpqCmcStatusInput4.
3
Minor (3)
cpqCmcStatusInput4:noSensor
cpqCmcStatusInput4.
4
Minor (3)
Seitenansicht 66
1 2 ... 62 63 64 65 66 67 68 69 70 71 72 ... 269 270

Kommentare zu diesen Handbüchern

Keine Kommentare