Removing the fan cage
To remove the component:
1. Power down the server (see
Powering down the server on page 16).
2. Remove all power:
a. Disconnect each power cord from the power source.
b. Disconnect each power cord from the server.
3. Extend the server from the rack, (see
Extending the server from the rack on page 17) or remove the
server from the rack.
4. Remove the access panel (see
Removing the access panel on page 18).
5. Remove the fan cage.
CAUTION: Do not operate the server for long periods with the access panel open or removed. Operating the
server in this manner results in improper airflow and improper cooling that can lead to thermal damage.
IMPORTANT: For optimum cooling, install fans in all primary fan locations. For more information, refer to
the fan locations table, (see
Hot-plug fans on page 14).
To replace the component, reverse the removal procedure.
20 Chapter 3 Operations