(Optional) Sensor Base Stations 45
9.
Select the Basic tab, and then select Download to transfer the new settings into the Chilled Water Base
Station.
10. Select OK to save the configuration settings and close the System Configuration window.
Testing the configuration
The 4mA and 20mA calibration values are factory set and must not be modified. If you modify these
calibration values and select Download, you will override the 4-20mA factory preset.
You can test the analog flow meter output for troubleshooting purposes. The Test field represents the Flow
Meter 4-20mA analog output value, but not the flow rate. The minimum value is 4 and the maximum value
is 20.
NOTE: Do not select Download during the testing or calibration process.
To test the calibration:
1. Select the Calibration/Test box. The Calibration and Test fields are now active.
2. Using whole numbers, adjust the Test field.
3. Verify the flow rate on the console matches the calibration of your flow rate.
Example: