Item
Area/
condition Yes No
Comment/
Date
Cooling considerations
24 Can the room temperature be maintained between the
recommended 18°C (64.4 °F) Min.27°C (80.6 °F) Max.
and allowable 15°C (59 °F) Min.32°C (90 °F) Max.
(up to 5000 ft) Derate 1°C/1000 ft
above 5000 ft and up to 10,000 ft
25 Can humidity level be maintained at the recommended level of
5.5°C (41.9°F) dew point to 60% relative humidity and 15°C (59°F) dew point, with an allowable
humidity levels of 20% to 80%
26 Are air-conditioning filters installed/clean?
Water preparation considerations
27 Has the water been tested for acceptable quality for use in the
MCS 5042?
28 If the water quality is unacceptable, have adequate treatment and
filtration measures been put into place?
29 Have the water temperature and flow been evaluated?
30 If temperature and flow are not adequate, have supplemental chiller units
and water pumps been implemented to achieve ample performance?
31 Has an adequately sized water-to-water heat exchanger been implemented
to provide a dedicated water loop to the MCS 5042?
32 Has piping of an appropriate diameter, material, and pressure tolerance
been installed to reach the back of each MCS 5042?
33 Is there a provision for fluid collected from the condensation and overflow
hoses at each MCS 5042?