Note:
The power requirements discussed in this guide are for the fans and
electronics for the MCS 5042 only. Data processing components such as
servers, storage, and network devices must be considered separately,
based on individual power requirements.
System grounding
HP server systems require two methods of grounding: power distribution grounding for safety, and
high-frequency signal grounding for equipment performance. Power distribution grounding involves
the main building electrical service entrance, electrical conduit, facility power panels, and equipment
cabinets (including the MCS 5042), which must be grounded, using green/yellow insulated wire
conductors according to the applicable electrical codes. High-frequency grounding consists of using
ground return conductors for intra-cabinet and inter-cabinet signal interconnects, as well as chassis
and cabinet grounding.
For MCS 5042 and server systems installed on a raised floor, the floor assembly must be electrically
grounded to form a complete ground grid. An optimum raised-floor grounding solution is shown in
Figure 15.
Each floor panel must have at least one supporting pedestal grounded to the power panel and
another pedestal grounded to the MCS 5042. The central ground connection of the MCS 5042 is
located in the bottom rear of the IT rack. This broadband solution provides grounding for maximum
safety and performance.
Figure 15: Central ground stud location inside the IT rack