43
Item Description Specifications
Hannifin, FBMB8-1/4 Metrulok fitting, Festo QB-1/4-5/16-U or equivalent and
installed by plumbing contractor, typical 1.
14 Hose barb Type: 12.7 mm (0.50 inch) I.D. hose barb x ¾-inch male NPT, Parker Hannifin,
125HBL-8-12, fitting or equivalent and installed by plumbing contractor, typical 1.
15 Hose Type: 8 mm (0.31 inch) outer-diameter (O.D.) flexible hose supplied with MCS 5042.
16 Hose Type: 9 mm (0.35 inch) inner diameter flexible hose supplied with MCS 5042.
17 Filter 1μm filter is recommended for optimal long-term performance of the MCS 5042. A
cartridge or bag filter could be used in a full flow or side stream flow configuration.
Watts
®
FM4X2 stainless steel housing or equivalent. Provide dielectric unions on both
connections. Provide pleated cartridge rated for 1 μm. Depending on water quality,
multiple units in parallel might be required.
18 Manual air vent Type: 19.05 mm (0.75 inch) two-piece, full-port, brass ball valve with chrome plated
brass ball, PTFE seats, and steel handle, with threaded connections.
Pressure rating: 600psi WOG, 150psi WSP.
Watts
®
FBV-3C or equivalent
19 Nipple Type: 19.05 mm (0.75 inch_ brass close nipple.
20 Cap Type: 19.05 mm (0.75 inch) brass cap with chain.
21 Test plug Type: Corrosion-resistant brass body with core inserts, gasketed and threaded cap,
with extended stem for units to suit piping insulation thickness.
Watts
®
TP or equivalent.
Typical plumbing installation guidelines
Installation service for this MCS 5042 is order number UE005E.
Contractors shall install all valves, strainers, and other piping components to the specifications
provided in the Chapter 2 sectionPiping approaches.” All components shall be readily accessible.
Contractor shall flush all lines of debris and cap prior to MCS 5042 installation.
Contractors shall furnish and install Armacell AP/Armaflex® closed-cell elastomeric thermal
insulation with minimum 25 mm (1 inch) minimum wall thickness on all customer piping and fittings.
Contractors shall furnish and install similar insulation type with minimum 6.4 mm (0.25 inch) wall
thickness for MCS 5042 chilled water hoses and fittings. The MCS 5042 hoses have a 45 mm
(1.75 inch) outer diameter and a bolt clamp that is 76 mm (3 inches) wide, 57 mm (2.25inches)
high and 51 mm (2 inches) deep on the side that must be connected to the infrastructure pipe. All
insulation joints shall be taped with AP/Armaflex® Insulation Tape, 3 mm (1/8 inch) thick x 50 mm
(2 inches) wide x 9.1 m (30 feet) long. Mitered fittings must be cemented with Armaflex® 520
Adhesive.
HP MCS 5042 condensate and overflow hoses do not require insulation.
Filters might require a minimum of 762 mm (30 inches) clearance under the floor for installation. If
the filters cannot be installed under the floor due to space constraints, they can be placed upstream
of the piping system.
Caution:
The water supply system feeding the MCS 5042 must capable of
withstanding the following situations:
Deadheading (operating with a closed line)
Operation with rapid and frequent changes in flow requirements
Operation over long periods of time with zero water flow.