Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Reset the EMU.
3. Observe the EMU to ensure the error is corrected.
4. If resetting the enclosure did not correct the problem, contact your H P authorized service
representative.
0.7.01.12 NONCRITICAL condition—EMU cannot read NVRAM data
The EMU is unable to read data from the NVRAM. This condition report remains active until the problem
is corrected
.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Reset the EMU.
3. Observe the
EMU to ensure the error is corrected.
4. If resetting the enclosure did not correct the problem, contact your H P authorized service
representative.
0.7.01.13 UNRECOVER ABLE condition—EMU load failure
The EMU Field Programmable Gate Array (FPGA) that controls the ESI bus failed to load information
require d for EMU operation. This condition report remains active until the problem is corrected.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Reset the EMU.
3. Observe the EMU to ensure the error is corrected.
4. If resetting the enclosure did not correct the problem, contact your H P authorized service
representative.
0.7.01.14 NONCRITICAL condition—EMU enclosure address
Either the enclosure address is incorrect or the enclosure has no address. Possible causes include a
defecti
ve enclosure address bus cable, an incorrectly connected cable, or a defective enclosure address
bus enclosure ID expansion cable. This condition report remains active until the problem is c orrected.
Complete the following procedure to correct this problem:
1. Record all six characters of the condition report.
2. Remove
and reconnect the cable between the address bus enclosure ID expansion cable and the
EMU.
NOTE:
The EM U display may not display a change in condition for up to 30 seconds.
3. Observe the EMU to ensure the error is corrected.
4. If the problem is not corrected, remove and reinstall the lower and upper terminators, and all the
enclosure ID expansion cable-to-enclosure ID expansion cables.
5. Observe the EMU to ensure the error is corrected.
6. Reset the EMU, then observe the EMU to ensure the error is corrected.
7. If resetting the EMU did not correct the problem, contact your HP authorized service representative.
130
EMU-generated c ondition reports