5. Verify that the ambient temperature range is +10 °C to +35 °C (+50 °F to +95 °F). Adjust as
necessary.
6. Observe the EMU to ensure the error is corrected.
7. If unable to correct the problem, contact your authorize d service representative.
0.4.en.03 NON
CRITICAL condition—Low temperature
This condition report indicates that an element temperature is approaching, but has not reached, the low
temperature CRITICAL threshold. Continued operation under these conditions may result in a CRITICAL
condition. T
his condition report remains active until the problem is corrected.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Verify that the ambient temperature range is +10 °C to +35 °C (+50 °F to +95 °F). Adjust as
necessary.
3. Observe the EMU to ensure the error is corrected.
4. If the ambient temperature is correct and the problem persists, contact your Authorized Service
Represent
ative.
0.4.en.04 C RITICAL condition—Low temperature
This condition report indicates that an element temperature has reached the low temperature CRITICAL
threshold. HP recommends correcting this error to prevent affecting other elements. This condition
report remains active until the problem is corrected.
Complete the following procedure to correct this problem.
1. Record all six characters of the condition report.
2. Verify that the ambient temperature range is +10 °C to +35 °C (+50 °F to +95 °F). Adjust as
necessary.
3. Observe the EMU to ensure the error is corrected.
4. If the ambient temperature is correct and the problem persists, contact your authorized service
representative.
0.4.en.05 UNRECOVERABLE condition—High temperature
This c ondition report indicates that the EMU has evaluated the temperature of the three temperature
groups
(EMU, disk drives, and power supplies), and determined that the average temperature of two
of the t
hree groups exceeds the critical level (use HP Command View EVA to view the temperature
thresholds) . Under these conditions the EMU starts a timer that will automatically shut down the enclosure
in seven minutes unless you correct the problem. Enclosure shutdown is imminent!
CAUTI
ON:
An aut
omatic shutdown and possible data corruption may result if the procedure below is not performed
immediately.
Complete the following procedure to correct this problem.
1. Ensure that all d isk drives, I/O modules, and power supply elements are fully seated.
2. Ensure that all blowers are operating properly.
3. Verify that the ambient temperature range is +10 °C to +35 °C (+50 °F to +95 °F). Adjust as
necessary.