Cold-aisle containment
In a cold-aisle containment system, two ITE rows face front-to-front, with the cold air coming up
through vented floor tiles of the common aisle. Cold air is isolated from the rest of the room air with
curtains and/or Plexiglas panels (Figure 6). This ensures that only cold air is drawn into the ITE racks.
The warm exhaust air exits the rear of the racks and is collected conventionally by the CRAHs.
Figure 6: Cold-aisle containment strategy
Cold-aisle containment is generally the easiest strategy to implement in a data center. There are no
restrictions for cable trays above the racks, and IT systems are easily scalable. But because much of
the data center room is at the hot air stream temperature, cold air meant to cool personnel in the
room will mix with the warm air from the ITE racks, resulting in cooler air returned to the CRAH. Low
return-air temperature can reduce cooling system efficiency, causing it to use shorter compressor
cycles and/or re-adjust the chilled-water flow more often.
If you retro-fit an existing data center with an air containment strategy, you must adhere to fire codes.
Fire suppression systems must have access to the face of the ITE racks.
Basic room requirement:
Raised floor
ITE racks
CRAH