HP Apollo 8000 iCDU Rack Schnellstart Anleitung Seite 12

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 48
  • Inhaltsverzeichnis
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 11
Overview 12
Parameter Value Comments
Rated input current
380VAC source415VAC 32A
per input meter
480VAC source24A per input
meter
Per line cord, two cords per power shelf, two
shelves per IT rack
Maximum inrush current
Less than 2 times the peak full load
current at any line condition
Per line cord
Dropout/hold-up time at
minimum line voltage
20 ms
Circuit breaker rating
380-415VAC source 32A
480VAC source30A
Per cord
Power factor
> 0.98 At all loads above 20%
Ground leakage current
<3.0mA Per cord
Maximum power
consumption (full IT rack)
79,775W capable power shelf This is the maximum power at the input of
the HVDC power shelves. There are two
power shelves per rack, each with dual
3-phase AC feeds.
Power cords
(included with power
shelves)
220/380 -240/415VAC
277/480VAC
3 meter, 8AWG, 5-wire with IEC 60309-
32
plug
3 meter, 8AWG, 5-wire with NEMA
L22-30P plug
The following table lists the electrical specifications for the HP Apollo 8000 iCDU Rack.
Parameter Value Comments
Operating Voltage
Minimum
Maximum
220/380VAC, 3 phase with N + PE
288/480VAC, 3 phase with N + PE
There are two CDU versions:
North AmericanSupports 480VAC
InternationalSupports 380VAC to
415VAC
AC line frequency
50/60 Hz
AC line phase
Three phase
Rated input current
480VAC source7.1 A
380VAC to 415VAC source9.5
A
Per line cord
Maximum inrush current
580 A peak-to-peak available Per line cord
Circuit breaker rating
15 A Per cord
Power factor
Typical value = 0.80 At all loads
Maximum power
consumption
5.7 kVA Steady state
Power cords
30A
480VAC sourceNEMA L22-30P
watertight connector
380VAC to 415VAC sourceIEC
60309 watertight connector
Seitenansicht 11
1 2 ... 7 8 9 10 11 12 13 14 15 16 17 ... 47 48

Kommentare zu diesen Handbüchern

Keine Kommentare