Overview 10
HP Apollo 8000 iCDU Rack front and rear components
Item Description Purpose
1
Display panel Provides general cooling unit status
2
External communication
connections
Provides connection to external components and
networks
3
Control switch Allows override of pump control for maintenance and
testing
4
VFD display Displays pump frequency
5
Power switch Controls main power to the iCDU
6
Two-way facility water control
valve
Electro-mechanical valve that controls flow of facility
water
7
iCDU local HEX return, 3/4
female hose bibb
Secondary water that stays local to the iCDU
8
Water inlet 2-1/2" male
cam-lock
Secondary water in
9
iCDU drain, 3/4 male hose bibb Used to drain the iCDU
10
Secondary water inlet, 3/4
female hose bibb
Secondary water system fill
11
iCDU local HEX supply, 3/4 male
hose bibb
Secondary water that stays local to the iCDU
12
Water outlet 2-1/2" male
cam-lock
Secondary water out
13
Water inlet 2-1/2" male
Facility water in
14
Water outlet 2-1/2" male
cam-lock
Facility water out
Physical specifications
The table below lists the approximate physical specifications of a single HP Apollo f8000 Rack or HP Apollo
8000 iCDU Rack as received from the factory. For help in calculating the total weight of the rack, including
components, see "Floor loading considerations (on page 18)."
Kommentare zu diesen Handbüchern