Facility planning for implementation 78
available, the provided system pressure difference must be slightly higher than the maximum pressure loss
with a fully opened control valve.
Acceptable water quality specifications
Closed-loop water must not contain any lime scale deposits or loose debris. The water must have a low level
of hardness, particularly a low level of carbon hardness. Filters must be used to remove free floating
particulates and regularly maintained. The water must not be so soft that it corrodes the materials that it
comes into contact. You must periodically add new fresh water, and remove some of the enriched water. HP
recommends a #30 mesh filter for filtering water fed to the MCS-200/100 and a 1 µm filter for prolonged
performance.
The following values are water quality ranges required for continuous quality of performance.
Parameter Range
pH
7-9
Specific conductance at 25ºC (77ºF)
<2500 µmhos
Sulfur (SO
4
), total
<100 ppm
Chloride (Cl)
<50 ppm
Sulfide (S)
<10 ppm
Hardness (CaCO
3
), total
<200 ppm
Iron (Fe), total
<3.0 ppm
Manganese (Mn), total
<0.1 ppm
Bacteria
<1000 CFUs/ml
Residue on evaporation
<500 ppm
Turbidity
20
Corrosion inhibitor
Recommended
CAUTION: Contaminated water might cause decreased cooling capacity or disruption in
service. The water flowing into the MCS-200/100 unit must meet the guidelines stated in the HP
Modular Cooling System 200/100 Site Preparation Guide. Damage caused by contaminated
water is not covered by the MCS unit warranty.
If your water is out of range, consult a water quality expert.
HP recommends using particulate filtration on the dedicated water supply system connected to the
MCS-200/100 unit.
Additional water precautions
The following actions should be taken during the installation of the MCS-200/100:
Be sure all foreign matter and particulates are flushed from the system prior to installing the water kits
for the MCS-200/100.
Evaluate the short- and long-term system requirements against available water capacity.
Be sure your facility water loop is properly designed for liquid cooling systems and separate from the
sanitary water systems within your buildingfor example, bathroom, sink, or drinking water.