Facility planning for implementation 77
Flow rate versus delta pressure (water control valve fully open)MCS-100
Flow rate versus delta pressure (water control valve fully open)MCS-200
A minimum water pressure difference of 1.0 to 1.5 bar (15 to 20 psi) between facility supply and return is
required. The previous figures give the pressure difference with a fully opened control valve. In operation, the
control valve maintains the water flow to the MCS-200/100 by introducing pressure resistance to reduce
the flow to accommodate different water temperatures and cooling capacity. Therefore, the pressure loss in
operation appears higher than shown in the above figures. However, to have the full scale of water flow