Appendix A Specifications
130
Table A-2. Environmental Requirements
Parameter Conditions
Temperature
Operating
5° to 35° C (41° to 95° F)
NOTE
Subtract 1° C (2° F) from the maximum
temperature for each 609m (2,000 ft.) gain
above sea level
Subtract 3
° C (5° F) from the maximum
temperature if unit is installed in non-HP
enclosed cabinet
Non-operating -40° to +65° C (-40° to +149° F)
Humidity
Operating 20% to 80% relative humidity,
non-condensing
Non-operating 5% to 95% relative humidity,
non-condensing
Altitude
Operating -30 to 3,045 m (10,000 ft)
Non-operating -30 to 12,180 m (40,000 ft)
Thermal Output
Maximum
Operating
1,365 BTU/hr
NOTE The specifications and requirements listed above can vary if
you install a mass storage device in the HP Netserver that has
more stringent environmental limits than required for the
Netserver. Ensure the operating environment for any mass
storage devices you intend to install are compatible with the
Netserver’s environmental requirements.