3 Specifications
Environmental Specifications
ValueSpecification
Temperature range
1
-5 to 50 ºC ambient temperatureOperating
-40 to 70 ºCNon operating
Relative humidity (non-condensing)
2
5 to 90% relative humidityOperating
5 to 93% relative humidityNon operating
Altitude
Operating 40 ºC from sea level to 6,000 ft.
30 ºC from 6,000 ft. to 13,000 ft.
Earthquake Zone 4Seismic resistance
1
Temperature ratings are shown for sea level. No direct sunlight allowed.
2
Storage maximum humidity of 93% is based on a maximum temperature of 40°C.
Seismic Rack Specifications
ValueSpecification
36UU Height
26.7 in (67.8 cm)Width
1
39.4 in (100.0 cm)Depth
Top, BottomCable Entry
1200 lbs (544.3 kg)Max Load
500 lbs (226.8 kg)
485 lbs (219.9 kg) - R2 rack
Rack Weight
200 lbs (90.7 kg)Packaging and Pallet Weight
1
Including side panels.
Floor Space Requirements
RecommendedMinimum
Measurement cmincmin
13051.291.436Front (appearance side) clearance
13051.291.436Rear (service side) clearance
< 2.5< 1.0----Space between cabinets
68.627----Cabinet pitch
Environmental Specifications 15