LED and audible alarm troubleshooting
Genera
l Alarm
LED
On
Batter
y LED
Batter
y Fault
LED
Site
Wiring
Fault
LED
Utility
LED
Overloa
d LED
Audible
alarm
Can
alarm be
silenced
("Silencin
g an
audible
alarm"
on page
31)?
Condition
Off Off Off Off Green Off
No audible
alarm
N/A
UPS is in Operate
mode (on page 27)
Off Off Off Off
Flashin
g
green
Off
No audible
alarm
N/A
UPS is in Standby
mode (on page 27)
Off Off Off Off Red Off
On1 beep
every 5
seconds
Yes
UPS is in Auto-Bypass
mode (on page 28)
Flashing
red
Off Off Off Red Off
On1 beep
every 5
seconds
Yes
General alarm
conditionUPS is in
Auto-Bypass mode
("General alarm
condition" on page
42)
Off Off Off Off
Flashin
g red
Off
On1 beep
every 5
seconds
Yes
Bypass is out of range
(on page 43)
Off Off
Flashin
g red
Off Off Off
On1 beep
every 5
seconds
Yes
Battery test failure
("Battery condition"
on page 43)
Off
Flashin
g red
Off Off Off Off
On1 beep
every 5
seconds
No
Low battery (no utility
power) ("UPS is on
battery" on page 43)
Off Off
Flashin
g red
Off Off Off
On1 beep
every 5
seconds
Yes
Batteries are
disconnected ("Battery
condition" on page
43)
Off Red Off Off Off Off
On1 beep
every 5
seconds
Yes
On batteryNo utility
power ("UPS is on
battery" on page 43)
Seitenansicht 40