HP Insight ControlPower Management 6.3 User GuideHP Part Number: 504591-003Published: April 2011Edition: 1

Seite 2

Power delivery hierarchyPower is provided through a set of power delivery devices. Insight Control power management representsplaces that can be monit

Seite 3 - Table of Contents

• Rack PDU: Rack Power Distribution Unit - This represents the input power and multiple outputs to loadsegments.• Load Segment: This represents each o

Seite 4 - 4 Table of Contents

phaseWatts = phaseVoltage * phaseAmpsTotalCapacity = 3 * phaseWattsFor 1-phase:TotalCapacity = lineCurrent * lineVoltageConverting Watts to AmperesIf

Seite 5 - List of Tables

Security propertiesProtocols and ports numbersInsight Control power management uses the following ports or external interfaces to aid administrators i

Seite 6

• The Power Switch action is implemented with a mix of SSA tool invocations, as with Shutdown above;and calls to the Power State action, as described

Seite 7 - 1 Introduction

the maximum amount of resources, but it might affect the system performance if processor utilizationstays at or above 75% utilization.• HP Static High

Seite 8

An idle system consumes the same power (339 W) regardless of the Power Regulator mode.Additionally, the power consumed in HP Dynamic Power Savings Mod

Seite 9 - 2 Key concepts

new data center expansion can save your company thousands of dollars. Insight Control power managementprovides you the following advantages:• Knowledg

Seite 11 - Power Calculation

3 Managing power and cooling facilities in your data centerTask: Importing power configuration from third-party management softwareHP Insight Control

Seite 12 - Data Center Power Control

© Copyright 2004, 2011 Hewlett-Packard Development Company, L.P.Legal NoticesConfidential computer software. Valid license from HP required for posses

Seite 13 - Security properties

For a small data center, the data can be maintained manually in VIS format where a column in the Excelworksheet represents a rack and each cell is a s

Seite 14 - Power Regulator

you through the steps of configuring power management to provide you that holistic view, and help youunderstand and control your power and cooling req

Seite 15 - Power Regulator 15

1. Specify the position of each system or enclosure in a rack.a. If you maintain a database (for example, UCMDB or Excel worksheet) describing the gro

Seite 16 - 16 Key concepts

In the Power/Thermal Analysis views page,• Power Status Alerts are highlighted with severity icons to highlight the severity of the alert. Alerts forc

Seite 17 - Power Capping

or for the selected systems, you may wish to allocate a greater share of the cap headroom to productionsystems, and lesser cap headroom to test system

Seite 18

based upon your current hardware configuration is significantly lesser than estimates based upon faceplateratings, or even based on the HP Power Calcu

Seite 19

While the faceplate power is 1000 Watts, the Calibrated Max Power as measured by the hardware itselfis only 509 Watts, and based upon historical obser

Seite 20 - Importing

Then, determine the amount of power must be reclaimed to make the necessary power/thermal capacityavailable in the rack.When applying caps, use the fo

Seite 21

Task: Defining rules for external eventsData Center Power Control rules can be invoked manually or automatically using the mxexec command torespond to

Seite 22

4 TroubleshootingInsight Control power management fails to show the Power graph and I receivethe messageInsight Control power management could not com

Seite 23

Table of Contents1 Introduction...7Overview...

Seite 24

Insight Control power management fails to show the Power graph and Ireceive the messageInsight Control power management could notcommunicate with the

Seite 25

Insight Control power management.* Insight Control power management is supported.For the incorrect PDU/PDR settings, the message will be displayed a

Seite 26

When DCPC Shutdown rule is invoked on a managed node, the system doesnot shut down.When DCPC Shutdown rule is invoked on a managed node running on Win

Seite 27 - HP Systems Insight Manager

5 Support and other resourcesInformation to collect before contacting HPBe sure to have the following information available before you contact HP:• So

Seite 28

HP authorized resellersFor the name of the nearest HP authorized reseller, see the following sources:• In the United States, see the HP U.S. service l

Seite 29 - 4 Troubleshooting

Typographic conventionsThis document uses the following typographical conventions:Book titleThe title of a book. On the web, this can be a hyperlink t

Seite 31 - Incorrect iLO credentials 31

A Capability matrixFor using HP or third party non-managed or managed devices and servers, the available power managementcapabilities are given in the

Seite 33 - 5 Support and other resources

Glossaryadministrativerights userA user who is authorized for the All Tools toolbox on all systems, including the CentralManagement Server. This type

Seite 34 - Related information

Task: Defining rules for external events...28Task: D

Seite 35 - Typographic conventions

HP Systems InsightManagerProvides unified foundation management services for HP servers, storage, and network resourcesfrom a single console. Systems

Seite 36

The type of power cap is determined when selecting:• A single system, the cap is a static single-system cap.• Multiple systems, the cap is a static gr

Seite 37 - A Capability matrix

• Warning The system has a potential problem or is in a state that might become a problem.• Normal The system is functioning correctly.• Disabled The

Seite 38

IndexCconceptsData Center Power Control, 12data centers, 9Dynamic Power Capping, 17Enclosure Dynamic Power Capping, 17Power Capping, 17power delivery

Seite 39 - Glossary

List of TablesA-1 Insight Control power management capabilities...375

Seite 41

1 IntroductionOverviewHP Insight Control power management (power management) is a component of HP Insight Control to workon Windows, HP Insight Contro

Seite 43

2 Key conceptsData centers, racks, and power delivery devicesData centersHP Insight Control power management enables you to define the data center phy