Capstone Turbine Corporation 21211 Nordhoff Street Chatsworth CA 91311 USA
Product Specification: Model C200 - Capstone MicroTurbine
460045 Rev C (November 2008) Page 12 of 16
Capstone reserves the right to change or modify, without notice, the design, specifications, and/or contents of this document
without incurring any obligation either with respect to equipment previously sold or in the process of construction.
Air Flow Requirements at Full Load Power
Table 7 summarizes the nominal air flow requirements of the C200 MicroTurbine systems.
Table 7. Air Flow Requirements at ISO Conditions with Zero Back Pressure
Parameter All C200
Engine Inlet Air Flow
2,600 scfm
(73,600 slpm)
Engine Inlet Air Temp
(1) (2)
-20 to 50 °C
(-4 to 122 °F)
Electronics Controller Inlet Air Flow
(3)
3,600 scfm
(102,000 slpm)
Electronics Controller Inlet Air Temp
(2)
-20 to 50 °C
(-4 to 122 °F)
Notes:
(1) For C200 versions that include the external heat recovery module, minimum operating ambient temperature
may be higher, depending on heat recovery fluid characteristics. For water, minimum ambient temperature is 1.7 °C
(35 °F).
(2) The Electronics Controller inlet air temperature must be within 2 °C (3.6 °F) of the Engine inlet air temperature.
(3) Values are the same for all C200 configurations, including low pressure and dual mode versions with batteries.