HP Modular Cooling System Bedienungsanleitung Seite 31

  • Herunterladen
  • Zu meinen Handbüchern hinzufügen
  • Drucken
  • Seite
    / 84
  • Inhaltsverzeichnis
  • FEHLERBEHEBUNG
  • LESEZEICHEN
  • Bewertet. / 5. Basierend auf Kundenbewertungen
Seitenansicht 30
Management module 31
Warning Temperature Threshold—Temperature difference above Server Intake Temperature Set Point
for temperature warning message
Low Temperature Threshold—Temperature difference below Server Intake Temperature Set Point for
temperature warning message
The following values are displayed in the web interface for information only:
Fan Speed Target—Displays the percentage of the fan maximum speed
Water Valve—Displays the water valve state
Cooling Module 1 through 3—Displays the Server Intake and Server Exhaust Temperature and the
RPM of each cooling unit
Water Inlet Temperature—Displays the temperature of the water coming into the MCS unit to be
used to cool the servers
Water Outlet Temperature—Displays the temperature of the water after removing the server heat
Water Flow—Displays the value of the water flow in liters/gallons per minute
Management module components
The management module is located on the inside of the MCS front door.
Item Reference Description
1 C key Used to confirm warnings, critical alarms, and
configuration setting changes, as well as to turn off the
audible alarm. Press and hold the C key for five
seconds, or click the Clear Alarms button on the Web
interface Setup tab>General menu, to confirm these
situations.