23
Table 12. Electrical formulae
Desired Data Single Phase Three-Phase Direct Current
Kilowatts (kW)
I x V x PF
3 x I x V x PF
I x V
Kilovolt-Amperes
kVA
I x V
3 x V x E
Electric Motor
Horsepower
Output (HP)
I x V x Eff . x PF
3 x I x V x Eff . x PF
I x V x Eff .
Amperes (I)
When Horsepower
is known
HP x 746
HP x 746
3 x V x Eff . x PF
HP x 746
Amperes (I)
When Kilowatts
are known
kW x 1000
kW x 1000
3 x V x PF
kW x 1000
Amperes (I)
When kVA is
known
kVA x 1000
kVA x 1000
3 x V
Where:
V = Volts
I = Amperes
Eff = Percentage Efficiency
PF = Power Factor=