Operating specifications
This section provides some general specifications. For complete specifications, see the system site
preparation guide, available on the HP XP Disk Array website:
http://h18006.www1.hp.com/storage/xparrays.html
Temperature
Table 4 Temperature specifications
RangeTemperature range type
21 to 24 degrees C, 70 to 75 degrees FRecommended operating temperature range
16 to 32 degrees C, 61 to 89 degrees FOperating temperature
–10 to +43 degrees C, 14 to 109 degrees FNonoperating temperature range
–25 to +60 degrees C, –13 to +140 degrees F
Shipping and storage temperature (product
packed in factory packing)
10 degrees C per hour, 18 degrees F per hour
Temperature shock immunity (maximum rate of
temperature change)
At 40 degrees C, 104 degrees FOver-temperature warning
At 60 degrees C, 140 degrees FOver-temperature shutdown
Humidity
Protect the disk array from excessive humidity. You should not observe condensation in or around the
product under any conditions. There is no procedure for recovery from moisture condensation.
Table 5 Humidity specifications
Noncondensing relative humidity
(RH)
Humidity range type
50% to 55%
Recommended operating humidity range at 22 degrees C (71
degrees F)
20% to 80%Operating humidity range at 22 degrees C (71 F)
8% to 90%Nonoperating humidity range
5% to 95%
Shipping and storage humidity range (product packed in factory
packing)
Mechanical vibration
Maximum operating acceleration is 0.05G at a frequency range of 10 to 300 Hz.