HP mc-Series 5042 Rack User Guide Abstract This document is for the person who installs racks and rack products. This procedure is performed only by
Installation 10 Installing the MCS 5042 unit WARNING: The MCS 5042 unit and rack are shipped together on a heavy duty shock pallet weighing appr
Installation 11 6. Plug the network cable into the RJ-45 connector on the transfer switch in the top of MCS 5042 unit. 7. Plug the other end of th
Installation 12 WARNING: To reduce the risk of electric shock or damage to the equipment: • Do not disable the power cord grounding plug. The gro
Installation 13 12. If the rear extension is installed, this step is optional. Using two M6 trilobe flathead screws, secure the two brackets to the
Installation 14 WARNING: To reduce the risk of electric shock or damage to the equipment: • Do not disable the power cord grounding plug. The gro
Installation 15 b. In the password field, enter the password. The default password is Admin. The Main Menu screen appears. 7. Enter the product ID
Installation 16 a. From the Main Menu screen, enter 3 Factory Default. The Default Product Identification screen appears. b. To set the product ID
Installation 17 a. From the Main Menu screen, enter 1 Network Configuration. The Menu Network Configuration screen appears.
Installation 18 b. Enter 1 IP Configuration. The IP Configuration screen appears. c. To disable DHCP, enter 4 Enable/Disable DHCP. d. Enter 1 IP
Installation 19 a. Return to the Main Menu Network Configuration screen. b. Enter 4 Activate Actual Values. c. To reboot, at the prompt, enter y.
© Copyright 2012 Hewlett-Packard Development Company, L.P. The information contained herein is subject to change without notice. The only warranties
Installation 20 c. Click Sign In. 12. Click Setup>Accounts, and then change the default Web Admin and Web User passwords. 13. Click Save Sett
Installation 21 15. Optional: Enter an SSL key. 16. Click Save Settings. 17. To set up your trap receivers, click Setup>Management>Trap Rec
Installation 22 19. Optional, but HP-recommended: To set up your SNMP managers, click Setup>Management>SNMP Managers. 20. Click Save Setting
Installation 23 c. Click Sign In. 4. Click Setup>Network. a. To disable DHCP, click the radio button. The default setting is enabled. Whenever
Installation 24 g. Log in to the new IP address. 5. Click Setup>Accounts, and then change the default Web Admin and Web User passwords. 6. Cl
Installation 25 8. (Optional) Enter an SSL key. 9. Click Save Settings. 10. To set up your trap receivers, click Setup>Management>Trap Rece
Installation 26 12. (Optional, but HP-recommended) To set up your SNMP managers, click Setup>Management>SNMP Managers. 13. Click Save Settin
Installation 27 1. Route the water hoses from the HP Hook Up Kit through the floor cut-out, and then use a hose wrench to install each main hose to
Installation 28 c. Click Sign In. 4. Click Setup>Advanced. 5. In the Temperature Control field, select Manual, and then click Save Settings.
Installation 29 7. Turn on the water by opening the ball valves at the facility water line connections. 8. In the web interface, click the Home ta
Contents 3 Contents Overview ...
Installation 30 10. If necessary, remove trapped air from the heat exchanger by opening the bleeder valve on the top rear side of the cooling unit.
Automatic Door Release Kit 31 Automatic Door Release Kit Automatic Door Release Kit Overview The Automatic Door Release Kit is designed as a safety
Automatic Door Release Kit 32 To test the Automatic Door Release feature: 1. At the bottom of the screen, click the Door Opening Test button. A new
Management module 33 Management module Management module overview The HP mc-Series 5042 Rack has a management module, which can be accessed remotely
Management module 34 • Fan Module—Displays the Server Intake and Server Exhaust Temperature as well as the RPM of each fan • Water Inlet Temperatu
Management module 35 Item Reference Description 3 Traffic/link LED Used to display the network connection. • If the LED is green, a 10-MB connec
Management module 36 2. Enter the password in the password field. The default password is Admin. The Main Menu screen appears. Accessing the manag
Management module 37 Component Requirement Web browser on a client • Microsoft® Internet Explorer 8.0 • Red Hat Linux operating system (32-bit o
Management module 38 For instructions on changing the password, see the HP mc-Series 5042 Rack Web Interface User Guide. Only one Admin session and
Management module 39 Connecting an alarm device to the management module alarm relay An alarm device can be connected to the management module alarm
Contents 4 Environmental specifications ...
Management module 40 Alarm relay item Specification Maximum voltage DC, 24 V internal or DC, 30 V with external power connection
Serial interface 41 Serial interface HP Modular Cooling System Utility overview The HP Modular Cooling System Configuration Utility is used for ente
Serial interface 42 Option number Submenu Description 1 Network Configuration Enter or change network properties for the management modul
Serial interface 43 IP Configuration submenu Option number Submenu Description 1 IP Address Enter or change the IP address for the managem
Serial interface 44 Change Passwords submenu Option number Submenu Description 1 Console Password 'Admin' Change the Admin pas
Serial interface 45 Info page The Info page displays the following parameters: • IP Address • Subnetmask • Router/Gateway • MAC Address • SysN
Serial interface 46 Factory Default submenu Option number Submenu Description 1 Set to Factory Default Set the management module to facto
Serial interface 47 5. When a connection is established, press Enter and then log in. The Main menu for the management module appears. Follow the on
Operator display 48 Operator display Operator display overview The operator display provides information on the system operation, viewable on the ou
Operator display 49 Indicators Meaning Type of message Warning Solution: 1. Remove the fan unit. 2. Reinstall the same fan unit. If the warning
Overview 5 Overview Introduction The HP mc-Series 5042 Rack is an air and water heat exchanger that removes high levels of excess heat generated by
Operator display 50 Solution: Verify the water supply. Water temperature input is out of range Indicators Meaning Operator display alarm message W
Operator display 51 1. Verify the water supply. 2. Contact HP, or see the HP website (http://www.hp.com). Water flow valve is closed Indicators M
Operator display 52 Indicators Meaning Operator display alarm message Temperature too high Web interface alarm message Temperature too high Condit
Operator display 53 Temperature below threshold (Low Temperature Threshold field) Indicators Meaning Operator display alarm message Temperature to
Operator display 54 Indicators Meaning SNMP notification Critical Type of message Alarm Solution: 1. Verify the water supply and that the MCS 504
Operator display 55 Indicators Meaning Condition The water level has exceeded the permissible level of the condensation pump sensor. Modules or sen
Operator display 56 NOTE: To clear the condensation pump cycles warning, click Cooling System in the left navigation frame to access the Cooling
Frequently asked questions 57 Frequently asked questions HP mc-Series 5042 Rack frequently asked questions Question Answer What cooling capacity r
Frequently asked questions 58 Question Answer Is water prevented from entering the MCS 5042 unit if a pipe breaks? Yes, the MCS 5042 unit is physic
Troubleshooting 59 Troubleshooting HP mc-Series 5042 Rack troubleshooting Issue Resolution The water flow is low or not flowing. For more informat
Overview 6 Item Reference 7 Heat exchanger unit 8 Fan units 9 Management module Unit top view NOTE: For easier viewing, the canopies were re
Specifications 60 Specifications MCS specifications Item Specification Voltage 208/230 VAC +/- 10%, 50/60 Hz Maximum height (including the rack) 2
Specifications 61 Thermal and air flow performance Maximum thermal and air flow performance parameters Single rack Dual rack (Specification per r
Replaceable parts and maintenance and service information 62 Replaceable parts and maintenance and service information Obtaining replaceable parts F
Water quality and leveling requirements, and condensation management 63 Water quality and leveling requirements, and condensation management Water q
Water quality and leveling requirements, and condensation management 64 Parameter Range Corrosion inhibitor Recommended If your water is out of ra
Water quality and leveling requirements, and condensation management 65 Condensation management Any condensation that forms is collected in each ind
Support and other resources 66 Support and other resources Before you contact HP Be sure to have the following information available before you call
Support and other resources 67 providers or service partners) identifies that the repair can be accomplished by the use of a CSR part, HP will ship
Support and other resources 68 Pour plus d'informations sur le programme CSR de HP, contactez votre Mainteneur Agrée local. Pour plus d'in
Support and other resources 69 HINWEIS: Einige Teile sind nicht für Customer Self Repair ausgelegt. Um den Garantieanspruch des Kunden zu erfüllen,
Configuration factors 7 Configuration factors Optimum environment and site preparation CAUTION: Contaminated water might cause decreased cooling
Support and other resources 70 sustituciones que lleve a cabo el cliente, HP se hará cargo de todos los gastos de envío y devolución de componentes
Support and other resources 71 Opcional – Peças cujo reparo feito pelo cliente é opcional. Essas peças também são projetadas para o reparo feito pel
Support and other resources 72
Support and other resources 73
Regulatory compliance notices 74 Regulatory compliance notices Safety and regulatory compliance For safety, environmental, and regulatory informatio
Acronyms and abbreviations 75 Acronyms and abbreviations CSR Customer Self Repair DHCP Dynamic Host Configuration Protocol MCS modular cooling sys
Documentation feedback 76 Documentation feedback HP is committed to providing documentation that meets your needs. To help us improve the documentat
Index 77 A accessing the management module 35, 36 alarm relay 39 Alarms and warnings 48 authorized reseller 66 Automatic Door Release Kit
Index 78 spares 62 specifications 60, 61 specifications, environmental 60 support 66 T technical support 66 telephone numbers 66 Tempera
Installation 8 Installation MCS 5042 kit contents • HP mc-Series 5042 Rack unit installed on an HP Rack (1) • Automatic Door Release kit (1) • Re
Installation 9 Hardware kit contents If any of the following items are missing or damaged, contact your HP authorized reseller. Item Description